
105/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
10 Connection to load controllers
25.09.2013
10.3 Manual output
A manual output can be set with the
Normal display
of the display and operating unit or
via the PC software.
Manual output via the display and operating unit
Manual output can be activated or adjusted by keeping the
F
button depressed for at
least 1 second and by pressing the
+
or
–
button.
Output
0
means
Manually off
.
As long as manual output is active, the output appearing on the normal display blinks.
To deactivate and to change to automatic operation, press
Esc
for 3 seconds.
If
Manually off
is activated, it is stored via mains OFF.
On power return, the burner assumes the
Manually off
position (
OFF
blinking) (refer to
chapter
Operation
).
Fuel changeover resets the manual output to
Invalid
.
Exception:
Setting
Manually off
is maintained after fuel changeover also.
Activation of
Manually off
in operation
To activate
Manually off
, first run the system to the minimum output limit. Then, keep the
F
button depressed for at least
1 second and press the
–
button.
Manually off
is activated by releasing the
F
button and by pressing again the
–
button.
Caution!
Manually off
must not be used by itself to put a burner out of operation when
doing mounting work, or when the burner is not ready for operation. The safety
notes in chapter
Safety notes
must be observed!
Manual output via the PC software
Refer to description of the PC software (J7352).
10.4 Output with curve settings
To set the curves via the display and operating unit or the PC software, a special
parameterization output is provided. Using this output, it is also possible to approach the
point of ignition. The output is delivered automatically and cannot be set manually. It is
only mentioned here for the sake of completeness.