17 Special feature: Burner identification (ID)
25.09.2013
17 Special feature: Burner identification
(ID)
The OEM must assign an individual burner identification to every burner. This ensures
that, during backup / restore, incompatible parameter sets cannot be copied between
different burners (also refer to documentation on ACS410 PC software chapter
Backup /
Restore
and in this document chapter
Backup / Restore
).
No. Parameter
113 Burner
identification
18 Connection to superposed systems
18.1 General information and building automation
functions
Communication with a BAC system is made possible via a data link using the COM X92
port and a special interface with galvanic separation and physical bus level adaptation.
This port can be used for connection of a Modbus, depending on the configuration
made.
OCI412.10
RS485
Modbus
LMV...
COM
X92
Figure 90: Connection via COM X92 to superposed systems
Note
Breakdown of bus communication
If the basic unit detects a breakdown of bus communication, the BAC system must
rewrite the value upon restoration of communication for the Modbus operating mode
and predefined target output