
230/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
29 Parameter list LMV36...
25.09.2013
Par.
Parameter
Number of
Type
Edit
Value range
Resolution
Default
Password level
no.
LMV36...
elements
Min
Max
setting
Bit 4 = 16: Fuel valve 2
Bit 5 = 32: Fuel valve 3 / pilot valve
951 Mains
voltage
(normalized)
AC 230 V: Voltage = value x 1.683
AC 120 V: Voltage = value x 0.843
1
Std_u8
Read only
0 V
255 V
1 V
0 V
SO
954 Intensity of flame
1
Std_u8
Read only
0%
100%
1%
0%
Info / Service
960 Actual flow rate (m³/h, l/h, ft³/h, gal/h)
1
Std_u16
Read only
0
6553.5
0.1
0
Info / Service
961 Phase (state for external module and display)
1
Std_u8
Read only
0
255
1
0
Info / Service
981 Error memory: Code
1
Std_u8
Read only
0
255
1
0
Info / Service
982 Error memory: Diagnostic code
1
Std_u8
Read only
0
255
1
0
Info / Service
992 Error
flags
10
Hex_32
Reset
0
0xFFFFFFFF 1
0
SO
Legend
Std_u8
8 bit integer, not signed
Std_u16
16 bit integer, not signed
Std_u32
32 bit integer, not signed
Std_s8
8 bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of
-1
!
Std_s16
16 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of
-1
!
Std_s32
32 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of
-1
!