29/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
4 Technical data
25.09.2013
4.1.2 Terminal loading
Outputs
Total contact loading:
Rated voltage
AC 120 V, 50 / 60 Hz
Unit input current (safety loop) from:
- Fan motor contactor
- Ignition transformer
- Valves
- Oil pump / magnetic clutch
(optional via AGM60...)
Max. 5 A
Individual contact loading:
Fan motor contactor
Rated voltage
AC 120 V, 50 / 60 Hz
Rated current
1.6 A pilot duty output declaration to
UL372
Power
factor
Cos
>0.4
Alarm output
Rated voltage
AC 120 V, 50 / 60 Hz
Rated
current
1
A
Power
factor
Cos
>0.4
Ignition transformer
Rated voltage
AC 120 V, 50 / 60 Hz
Rated current
1.6 A pilot duty output declaration to
UL372
or
250 VA ignition output declaration to
UL372
Power
factor
Cos
>0.2
Fuel valves
Rated voltage
AC 120 V, 50 / 60 Hz
Rated current
1.6 A pilot duty output declaration to
UL372
Power
factor
Cos
>0.4
Operation display
Rated voltage
AC 120 V, 50 / 60 Hz
Rated current
0.5 A
Power
factor
Cos
>0.4
Safety valve (SV) (magnetic clutch / oil pump)
Rated voltage
AC 120 V, 50 / 60 Hz
Rated
current
2
A
Power
factor
Cos
>0.4
Connections for pressure switch
Rated voltage
AC 120 V, 50 / 60 Hz
Rated current
1.5 mA
Power
factor
---
Fuel feedback to LMV36... (X31-02 pin 1 or X31-02 pin 2)
IaMax
<10
mA
4.1.3 Analog output / load output X74 pin 3
Accuracy of output voltage
±1%