51/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
7 Basic unit
25.09.2013
For the input, a repetition counter can be parameterized. It can be used to set the
number of errors permitted until lockout occurs. The counter also impacts the gas
shortage program (refer to chapter
Repetition counter
).
No. Parameter
223
Repetition limit value gas pressure switch-min
1 = No repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
323
Repetition limit value gas pressure switch-min
1 = No repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Start release gas
If, at the same time, the input is used as a start release input (e.g. for an air supply
damper), it can be connected in series with the pressure switch.
When selecting
Valve proving via pressure switch-min
(parameter 236), function
Start
release gas
is not supported.
7.3.7 Oil pressure switch-min (Pmin) X9-04 (X5–01 on AGM60...)
Input for connection of a pressure switch-min for oil: If the plant does not require a
pressure switch-min, a wire link between terminal 2 and terminal 3 must be fitted.
Caution!
The OEM must check to see whether the burner can be operated without using
a pressure switch-min. This may necessitate a special approval, depending on
the application.
Pressure switch valve proving (PLT)
or oil pressure switch-min (Pmin)
LMV...
Bild 371e/1010
3
2
1
P LT
3
2
Oil
min
Figure 23: LMV36...: Oil pressure switch valve proving (P LT) X5-01
Pressure switch valve proving (PLT)
or oil pressure switch-min (Pmin)
LMV...
3
2
1
1
Bild 369e/1010
Oilmin
1
to
basic
un
it
F
uel
1
Fu
el
0
1
1
1
2
3
4
5
3
2
1
3
2
1
AGM60...
Figure 24: LMV36... with AGM60...: Oil pressure switch – valve proving (P LT) X5-01