100/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
9 Selection of operating mode
25.09.2013
No. Parameter
301
Fuel 1: Burner operating mode (fuel train, modulating / multistage, actuators,
etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = HO mod with circulation
¹)
24 = HO 2-stage with circulation
¹)
25 = HO mod without circulation control
¹)
26 = HO 2-stage without circulation control
¹)
27 = HO 3-stage without circulation control
¹)
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0