1.2.2 AGM60...
0,3
85
11
0
101
69
M4 (4x)
6,5
97
10 (2
x)
Bild 258e/0309
Figure 2: AGM60... note for mounting
Screwed
On a DIN rail
A = mounting B = removal
Mounting on DIN rails requires a
mounting clip!
If the unit is screwed on, following must be observed:
The AGM60… switch unit must be secured with fixing screws M4 (UNC32),
observing a maximum tightening torque of 1.8 Nm and using all 4 fixing points
The additional mounting surfaces on the housing must be used; they are provided
to improve mechanical stability and must fully rest on the mounting surface. The
flatness of the mounting surface must be within a tolerance band of 0.3 mm
Notes for mounting
Mounting method