222/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
29 Parameter list LMV36...
25.09.2013
Par.
Parameter
Number of
Type
Edit
Value range
Resolution
Default
Password level
no.
LMV36...
elements
Min
Max
setting
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod. sep. circulation ¹)
24 = Ho 2-stage sep. circulation ¹)
25 = Ho mod. without circulation ¹)
26 = Ho 2-stage without circulation ¹)
27 = Ho 3-stage without circulation ¹)
¹) Selected operating mode is not released for the basic unit.
With select: Error code 210 diagnostic code 0
321 Fuel 1 gas: Active detector of flame evaluation
0 = QRB
1 = ION / QRA
1 Selection
Edit
0 1 1 1
SO
322 Fuel 1 gas: Prepurging
0 = inactive
1 = active
1 Selection
Edit
0 1 1 1
SO
323 Repetition limit value gas pressure switch-min
1 = no repetition
1 Std_u8
Edit
1 16 1 1
SO