23 Operating the AZL2... unit
25.09.2013
23.4 Special
functions
23.4.1 Manual lockout
/reset
plus other button
P
V
h min s
%
B
ild
3
/07
07
Press
/reset
simultaneously
with any other
button.
The basic unit switches instantly to the lockout
position, irrespective of the operating position.
The display shows the fault status message,
except when in parameter setting mode.
23.4.2 Manual control (manual request for output)
P
V
h min s
%
B
ild
4
/07
07
Burner is in operation.
The display shows
oP:
on the left, the
percentage
of the current output on the right.
Example:
oP: 20.0
F
1 s
P
V
h min s
%
B
ild
5
/07
07
Press
F
for 1 s.
The display shows
LoAd:
, the current output
flashes.
F
and
or
P
V
h min s
%
B
ild
6
/07
07
Press
or
to adjust the required
manual output.
Example:
oP: 23.0
P
V
h min s
%
B
ild
7
/07
07
Release
F
.
The current manual output flashes, indicating
that manual control is activated.
ESC
P
V
h min s
%
B
ild
8
/07
07
Press
ESC
for 3 seconds to return to
automatic mode.
The output no longer flashes.
The display shows
oP:
on the left, the
percentage
value on the right.
Example:
oP: 23.0