225/248
Building Technologies Division
Basic documentation LMV36...
CC1P7544en
Infrastructure & Citiies Sector
29 Parameter list LMV36...
25.09.2013
Par.
Parameter
Number of
Type
Edit
Value range
Resolution
Default
Password level
no.
LMV36...
elements
Min
Max
setting
380
Repetition limit value loss of flame
1 = no repetition
2 = 1 repetition
1 Std_u8
Edit
1 2 1 1
OEM
381
Fuel 1 oil: Point in time oil is ignited
0 = short preignition (Ph38)
1 = long preignition (with fan) (Ph22)
1 Selection
Edit
0 1 1 0
SO
384 Fuel 1 oil: Postpurge time 3 (abortion if load controller ON)
1
Time
Edit
1 s
108 min
0.2 s
1 s
SO
385 Fuel 1 oil: gas pressure switch-min with «Lo Gp»
0 = inactive
1 = active
1 Selection
Edit
0 1 1 0
SO
400 Ratio curves
401 Ratio control curves fuel actuator (curve setting only)
13
Std_s16
Edit
0 °
90 °
0.1 °
0 °; 0 °; 15 °; undefined SO
402 Ratio control curves air actuator (curve setting only)
13
Std_s16
Edit
0 °
90 °
0.1 °
0 °; 90 °; 45 °; undefined SO
403 Ratio control curves VSD (curve setting only)
13
Std_s16
Edit
15 %
100%
0.1%
0%;
100%;
50%;
undefined
SO
404 Fuel 1: Ratio control curves fuel actuator (curve setting only)
13
Std_s16
Edit
0°
90°
0.1°
0°, 0°, 15°, undefined
SO
405 Fuel 1: Ratio control curves air actuator (curve setting only)
13
Std_s16
Edit
0°
90°
0.1°
0°, 90°, 45°, undefined
SO
406 Fuel 1: Ratio control curves VSD (curve setting only)
13
Std_s16
Edit
15 %
100 %
0.1 %
0 %, 100 %, 50 %,
undefined
SO
500 Ratio control
501 No-flame positions fuel actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3
Std_s16
Edit
0 °
90 °
0.1 °
Index
0
1
2
Value
0°
0°
15°
SO
502 No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
3
Std_s16
Edit
0 °
90 °
0.1 °
Index
0
1
2
Value
0°
90°
45°
SO
503 No-flame
speeds
VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
3 Std_s16
Edit
0% 100%
0.1% Index
0
1
2
Value
0%
100%
50%
SO