4. Parameter description
Parameter
4.39 Programmed operation mode (P.100~P.108, P.111~P.118, P.121~P.123,
P.131~P.138)
P.100 “Minute/second selection”
P.101~P.108 “Runtime of each section”
P.111~P.118 “Acceleration/deceleration time of each section”
P.121 “Run direction in each section”
P.122 “Cycle selection”
P.123 “Acceleration/deceleration time setting selection”
P.131~P.138 “Frequency of each section”
Related parameters
P.80~P.84, P.86
“
Multi-function terminals selection
”
P.8
“
Deceleration time
”
P.7
“
Acceleration time
”
P.21
“
Acceleration/deceleration
time increments
”
Parameter
Factory setting
Setting range
Remarks
100
1
0, 1
0
The running time minimum increment is 1
minute.
1
The running time minimum increment is 1
second.
101~108
0s
0~6000s
---
111~118
0s
0~600s
When P.21=0
0~6000s
When P.21=1
121
0
0~225
0: cycle function invalid;
1~8: run circularly
122
0
0~8
---
123
0
0, 1
---
131~138
0
0~400Hz (Note 4)
---
<Setting>
1. Programmed operation mode
• The calculation method of runtime and acceleration/deceleration time in each section is in the figure
below: