130
Appendix 1 Parameter list
Parameter list
Parameter
number
Name
Setting range
Minimum
setting unit
Default value
User setting
value
Reference
page
P.47
Second base frequency
0~400Hz, 9999
0.01Hz
9999
P44
P.48
Data length
0, 1
1
0
P59
P.49
Stop bit length
0, 1
1
0
P59
P.50
Parity check selection
0, 1, 2
1
0
P59
P.51
CR and LF selection
1, 2
1
1
P59
P.52
Number of
communication reties
0~10
1
1
P59
P.53
Communication check
time interval
0~999.8s, 9999
0.1s
9999
P59
P.54
AM terminal function
selection
0, 1
1
0
P83
P.55
Frequency monitoring
reference
0~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P83
P.56
Current monitoring
reference
0~500A
0.01A
Related output
current
P83
P.57
Retry coasting time
0~30s, 9999
0.1s
9999
P85
P.58
Retry voltage rising time
0~60s
0.1s
10s
P85
P.59
Selection of frequency
sources
0, 1
1
1
P75
P.60
Input signal filtering
constant
0~31
1
31
P86
P.61
Remote setting function
selection
0~3
1
0
P86
P.62
Zero current detection
level
0~200%, 9999
0.1%
5%
P88
P.63
Zero current detection
time
0.05~1s, 9999
0.01s
0.5s
P88
P.64
Reserved
P.65
Retry selection
0~4
1
0
P89
P.66
Stall prevention operation
reduction level starting
frequency
0~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P55
P.67
Number of retries at alarm
occurrence
0~10
1
0
P89
P.68
Retry waiting time
0~360s
0.1s
6s
P89
P.69
Retry accumulation times
0
0
0
P89
P.70
Special regenerative brake
duty
0~30%
0.1%
0
P58