81
4. Parameter description
Parameter
Parameter
Factory
setting
Setting
range
Remarks
85
5
0~10
3
OL (Overload detection): Signal will be output once the
current limit function is triggered.
4
OMD (Zero current detection): If the output current
percentage of the inverter is less than the set value of P.62,
and lasts for the pre-defined time (the setting value of
P.63), OMD will output signal.
5
ALARM (Alarm detection): Alarm detection
6
PO1 (Section detection): In programmed operation mode,
PO1 signal will be output in the end of each section.
7
PO2 (Periodical detection): In programmed operation
mode, PO2 signal will be output in the end of each cycle.
8
PO3 (Pause detection): In programmed operation mode,
PO3 signal will be output when the inverter pauses.
9
BP (Inverter output): Switch between the inverter
operation and commercial power-supply operation
function, when the inverter operation, BP will output
signal.
10
GP (Commercial power-supply output): Switch between
the inverter operation and commercial power-supply
operation function, when the commercial power-supply
operation, GP will output signal.
120
0
0.1~3600s
---
< Setting >
• When P.120=0, if the set condition of P.40 (P.85) is met, the signal will be output directly.
• When P.120=0.1~3600, if the set condition of P.40 (P.85) is met, the signal will be output after the
set time.
For example: FU (Output frequency detection) function (For example: P.42/P.43=40Hz)
P.120
P.120
Output
frequency
(
Hz
)
40
Time
(
s
)
At least 100ms
OFF
ON
ON
OFF
OFF
FU
Output frequency
detection value
(
P.42/P.43
)