75
4. Parameter description
Parameter
.
Parameter
Factory setting
Setting range
Remarks
37
0 r/min
0.1~5000r/min
0: output frequency
<Setting>
• The set value of P.37 is the mechanical speed of the inverter when its output frequency is 60Hz.
For example: If the transmitting belt speed is 950 m/minute when the inverter output frequency is
60Hz, P.37 shall be set to 950. In ‘output frequency monitoring mode’, the screen will
display the speed of the transmitting belt.
Note: 1. There’s minute discrepancy between the displayed mechanical speed and the actual one.
2. Please refer to Section 3-2 for detailed operation of the ‘operation panel working mode’.
3. When the output mechanical speed is more than 9998, the screen will display 9999.
4.19 Voltage signal selection and target frequency (P.38, P.59, P.73, P.76,
P.139, P.140, P.141)
P.38 “The maximum output Frequency (the target frequency is set by the input
signal across terminal 2-5/panel knob)”
P.59 “Selection of frequency sources”
P.73 “Voltage signal selection”
P.76 “Panel knob signal input frequency bias”
P.139 “Voltage signal bias”
P.140 “Voltage signal gain”
P.141 “ Bias polarity of voltage signal and
Reverse Motion of Negative Bias”
Related parameters
P.80~P.84, P.86
“Multi-function terminals selection”
P.79 “Operation mode selection”
P.194 “Bias of the input signal
across terminal 2-5”
P.195 “Gain of the input signal
across terminal 2-5”
P.189 “Default function”
Parameter
Factory setting
Setting range
Remarks
38
50Hz
1~400Hz (Note 4)
When P.189=1
60Hz
When P.189=0
59
1
0, 1
---
73
0
0, 1
0
The range for the input voltage signal
(terminal 2-5/4-5) is 0~5V.
1
The range for the input voltage signal
(terminal 2-5/4-5) is 0~10V.
76
0
0~400Hz (Note 4)
---
139
0%
0%~200%
---
140
100%
0.1%~200%
---
141
0
0~11
---