95
4. Parameter description
Parameter
Para-
meter
Termi
nal
Factory
setting
Setting
range
Value
name
Function
Instruction
86
RES
30
0~39
32
REX
Multi-speed
33
PO
In ‘external mode’, when PO
is ‘on’, programmed
operation mode is chosen.
34
RES_E
When
alarms occur,
external
Reset became effective
35
MPO
In ‘external mode’, when
MPO is ‘on’, manually
operation
circle mode is
chosen
36
TRI
When TRI is on, triangle
Wave function is chosen
37
GP_BP
Automatic switchover
frequency between inverter
and commercial
power-supply operation
38
CS
Manual swicth to commercial
power-supply
39
STF/STR
+STOP
In ‘external mode’, it is used
with RUN. The inverter runs
reverse when STF/STR is
‘on’, stop when STF/STR is
‘off’. If you need runs
forwards, you should RUN
again.
Note: 1. The default values are: P.80=2 (RL), P.81=3 (RM), P.82=4 (RH), P.83=0 (STF), P.84=1 (STR), P.86=30
(RES).
2. When changing the value of P.80~P.84, P.86, the functions of the terminals are changed. For example,
P.80=2 means that the function of M0 is RL, but if P.80=8, its function changes to RT, as a second
function selection terminal, P.83=0 means that the STR terminal is chosen as running forward terminal,
when P.83=6, its function changes to ‘OH’, it is then external thermal relay terminal.
3. Wiring for external thermal relay (OH): In traditional wiring,
a thermal relay is added to the motor to prevent the motor
from being too hot. Its wring is on the right figure. When
the external thermal relay is separated, the inverter will
indicate alarm, and ‘OHT’ will be displayed on the screen.
4. There are 4 kinds of operating modes to drive the inverter (‘1’ means the terminal closes, ‘0’ means the
terminal opens, X=0,1,2,3,4,6):
(1). two-wire control mode1: