52
4. Parameter description
Parameter
<Setting>
• If P.14=4, suppose that P.19=220V, P.98=5HZ, P.99=10%, when the inverter is running at 5HZ, the
output voltage equals P.99
×
P.19=10%
×
220V=22V.
• If RT is ‘on’, P.46 ‘Second Torque Boost’ is valid.
P.14
=
0
Output frequency
P.0
0
P.3
Output voltage
P.19
Applicable to Constant torque loads (conveyer belt etc.)
P.14
=
1
P.0
0
P.3
P.19
Output voltage
Output frequency
Applicable to Variable torque loads (fans and pumps etc.)
P.14
=
2
P.0
0
P.3
P.19
Forward rotating
Reversely rotating
Output voltage
Output frequency
Ascending/descending loads
P.14
=
3
P.0
0
P.3
P.19
Forward rotating
Reversely rotating
Output voltage
Output frequency
Ascending/descending loads
P.14
=
4
0
P.0
P.98
P.162
P.164
P.166
P.168
P.99
P.169
P.167
P.165
P.163
P.19
P.3
Output voltage
(
%
)
Output frequency (Hz)
Whether it is high startup torque or descending torque
is due to the set values
(
Note 1
)
P.14=5
Output frequency
P.0
0
P.3
Output voltage
P. 19
A
P.98=3.0
0.1
When P.14=5, The value of A is 7.1%.