129
Appendix 1 Parameter list
Parameter list
Parameter
number
Name
Setting range
Minimum
setting unit
Default value
User setting
value
Reference
page
P.25 Speed 5
0~400Hz, 9999
0.01Hz
9999
P46
P.26 Speed 6
0~400Hz, 9999
0.01Hz
9999
P46
P.27 Speed 7
0~400Hz, 9999
0.01Hz
9999
P46
P.28
Output frequency filtering
constant
0~31
1
0
P56
P.29
Acceleration/deceleration
pattern selection
0, 1, 2
1
0
P56
P.30
Regenerative function
selection
0, 1
1
0
P58
P.31 Soft-PWM selection
0
、
1
1
0
P58
P.32
Serial communication
Baud rate selection
0, 1, 2
1
1
P59
P.33
Communication protocol
selection
0, 1
1
0
P59
P.34 Reserved
P.35 Reserved
P.36 Inverter station number
0~254
1
0
P59
P.37 Speed display
0~5000r/min
0.1r/min
0
P74
P.38
The maximum output
frequency(the target
frequency is set by the
input signal across terminal
2-5/panel knob)
1~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P75
P.39
The maximum output
frequency(the target
frequency is set by the
input signal across terminal
4-5)
1~400Hz
0.01Hz
50Hz/60Hz
(Note 2)
P79
P.40
Multi-function output
terminal pattern
0~10
1
0
P80
P.41 Up-to-frequency sensitivity
0~100%
0.1%
10%
P82
P.42
Output frequency detection
for forward rotation
0~400Hz
0.01Hz
6Hz
P83
P.43
Output frequency detection
for reverse rotation
0~400Hz, 9999
0.01Hz
9999
P83
P.44 Second acceleration time
0~360.00s/
0~3600.0s
、
9999
0.01s/0.1s
9999
P47
P.45 Second deceleration time
0~360.00s/
0~3600.0s
、
9999
0.01s/0.1s
9999
P47
P.46 Second torque boost
0~30%, 9999
0.1%
9999
P43