44
4. Parameter description
Parameter
4.2
The output frequency range (P.1, P.2, P.18)
P.1 “Maximum frequency”
P.2 “Minimum frequency”
P.18 “High-speed maximum
frequency”
Related parameters
P.13
“
Starting frequency
”
The upper limit and the lower limit of the output frequency can be restricted.
Parameter
Factory setting
Setting range
Remarks
1
120Hz
0~120Hz (Note 2)
---
2
0Hz
0~120Hz (Note 2)
---
18
120Hz
120~400Hz (Note 2)
---
P.1(P.18)
P.2
Output
frequency
(
Hz
)
Setting frequency(Hz
)
<Setting>
• If the target frequency
≦
P
.2,
the steady output frequency equals P.2.
• If P.2 < target frequency
≦
P
.1 (P.18), the steady output frequency equals target frequency.
• If P.1 (P.18) <target frequency, the steady output frequency equals P.1.
Note: 1. The ‘maximum frequency’ and the ‘high-speed maximum frequency ’are related with each other. If the
target upper limit frequency is in the range of 0~120Hz, P.1 must be used (the setting range of P.1 is
0~120Hz); if the target upper limit frequency is in the range of 120~400Hz, then P.18 must be employed
(the setting range of P.18 is 120~400Hz).
2. If P.187=1, P.1 and P.2 are in the range of 0~1000Hz, P.18 is in the range of 120~1000Hz
3. If P.1 < P.2, the steady output frequency will be clamped to P.1.
4. The set frequency value can not exceed the value of P.1.
4.3
Base Frequency and base Voltage (P.3, P.19, P.47)
P.3 “Base Frequency”
P.19 “Base Voltage”
P.47 “Second base frequency”
Related parameters
P.80~P.84, P.86
P.189
“
Default function
”
P.14
“
Load pattern selection
”
“
Multi-function terminals selection
”