99
4. Parameter description
Parameter
frequency
Run forward
Run reverse
P.111
P.101
P.112
P.113
P.114
P.115
P.102
pause
P.103
P.104
P.116
P.105
P.106
P.117
P.107
P.118
P.108
P.118
• The run direction is set in binary form (8-bit), then translated to decimal form and stored in P.121.
‘1’ means run forward, and ‘0’ means run reverse. The highest bit is the run direction of section 8,
and the lowest bit is the direction of section 1.
For example: Suppose that section 1: run forward, section 2: run reverse, section 3: run reverse,
section 4: run forward, section 5: run reverse, section 6: run forward, section 7: run
forward, section 8: run reverse, than the value in binary form is 01101001:
P.121=0×27+1×26+1×25+0×24+1×23+0×22+0×21+1×20=105
• When P.122=0, it won’t run circularly.
• When the value of P.122 is 1~8, it is the initialization section of the cycle running.
For example: When P.122=3, the inverter will run circularly from the third section to the eighth
section after it finishes its running from the first section to the eighth section.
When P.123=0, the acceleration time is determined by P.7, and the deceleration time is
determined by P.8.
When P.123=1, the acceleration time and deceleration time are both determined by
P.111~P.118.
2.
Manually operation
circle mode
RL
INV
SD
Manually operation circle mode terminals wiring pattern
• Between RL and SD, connect an impulse type switch.
• After power on, setting P.80=35 according to the terminals wiring, in this time, inverter is standby.
• The mode of operation is in the figure below: