7
2.
Introduction of Shihlin Inverter
Introduction of Inverter
2.2 Common specification (Inverter characteristics)
Control method
SVPWM control, V/F control, facility vector control, Speed sensorless
vector control.
Output frequency range
0.2~1000Hz (The starting frequency setting range is 0~600Hz). Please
refer to P.187 in Chapter 4.
Resolution for
setting frequency
Digital
setting
When P.187=0, if the frequency set value is below 100Hz, the resolution
will be 0.01Hz. If the frequency set value is above 100Hz, the resolution
will be 0.1Hz. When P.187=1, the resolution of frequency will be 0.1Hz.
Analog
setting
When setting DC 0~5V signals, the resolution will be 1/500;
When setting DC 0~10V or 4~20mA signals, the resolution will be
1/1000.
Output frequency accuracy 0.01Hz
Voltage / frequency output
characteristics
Base voltage (P.19), base frequency (P.3) can be arbitrarily set.
Constant torque model, variable torque model can be selected (P.14).
Start torque
150% (1Hz): when use the facility vector control.
Torque boost
The torque boost setting range is 0~30% (P.0), auto boost, slip
compensation.
Acceleration/deceleration
curve characteristics
The acceleration/deceleration time (P.7, P.8), resolution:0.01s/0.1s,
switch by P.21. The setting range is 0.01~360s or 0.1~3600s for
selection. Different ‘acceleration/deceleration curve’ model can be
selected (P.29).
DC braking
The DC braking action frequency is 0~1000Hz (P.10); the DC braking
time is 0~60 Seconds (P.11); and the DC braking voltage is 0~30%
(P.12). Linear braking and Idling braking selection (P.71).
Stalling protection
The stalling protection level can be set to 0~400% (P.22).
Target frequency setting
Operation panel setting, DC 0~5V signal setting, DC 0~10V signal
setting, DC 4~20mA signal setting, 2 voltage input or one voltage and
one current input to select. Multi-speed stage levels setting,
Communication setting.
PID control
Please refer to P.170~P.183 in Chapter 4.
Multi-function control
terminals
Motor starting (STF, STR), the second function (RT), ‘16-speed
operation’(RL, RM, RH, REX), external thermal relay (OH), reset
(RES), etc. (can be set by the user (P.80~P.84, P.86))
Multi-functi
on output
terminals
Multi-function
output
terminals (SO,
SE)
P.40
Inverter running (RUN), output frequency detection (FU), Up to
frequency (SU), overload detection (OL), zero current detection
(OMD), alarm (ALARM), Section detection (PO1), Periodical
detection (PO2), and Pause detection (PO3), Inverter output (BP),
Commercial power-supply output (GP).
Multi-function
output relay
P.85
Multi function
analogy meter
Multi-function DC (0~10V)(AM)
output: output frequency, output current (P.54).