Note: 1. When need restart function, P.150 must be setted.
2. When the value of P.150 is not 0, default linear acceleration/deceleration curve.
3. The detection of rotation of P.150 is only to immediate frequency search.
4. This function is valid in V/F curve. It means P.300 must be set to 0.
4.26
Input signal filter constant (P.60)
P.60 “Input signal filter constant”
● When the running frequency is set by a voltage signal or a current signal, the voltage/current signal
would be processed by an A/D converter. Due to the effect of device accuracy or noises, the
external voltage signal or current signal may fluctuate and thus the running frequency fluctuates.
● The ‘Input signal filter constant setting P.60’ is used to filter the fluctuation of the running
frequency caused by the above factors. The larger the P.60 set value is, the better the filter
performance, but larger delay is resulted in.
Parameter
Factory setting
Setting range
Remarks
60
31
0~31
---
4.27
Remote control function (P.61)
P.61 “Remote setting function selection”
Related parameters
P.18 “High-speed maximum
frequency”
P.1 “Maximum frequency”
P.8 “Deceleration time”
P.7 “Acceleration time”
P.44 “Second acceleration time”
P.45 “Second deceleration time”
● If the operation box is located away from the control box, you can use contact signals to perform
continuous variable-speed operation, without using analog signals, when in ‘external mode’,
‘combined mode 1’ or ‘combined mode 5’.
Parameter
Factory
setting
Setting
range
Remarks
Set
value
Remote set
function
Frequency setting storage function
61
0
0~3
0
No
---
1
Yes
Yes
2
No
3
No
(the remote setting frequency is cleaned
out by STF/STR ‘turn off’)