118
4. Parameter description
Parameter
Parameter
Factory setting
Setting range
Remarks
288
0
0~12
1~12 are the value of P.288 which are
corresponding to abnormal number of alarm code
E1~E12 the P.289 display.
289
0
---
290
0
0~5
If P.290=1, P.291 correspond to display frequency
for the latest alarm occurred.
If P.290=2, P.291 correspond to display current for
the latest alarm occurred.
If P.290=3, P.291 correspond to display output
voltage for the latest alarm occurred.
If P.290=4, P.291 correspond to display the
accumulation rate of temperature for the latest
alarm occurred.
If P.290=5, P.291*100 correspond to display busbar
voltage for the latest alarm occurred.
291
0
---
If the value of P.288 and P.290 are 0, P.289 and P.291will display 0 too.
The abnormal number of the alarm code:
Abnormal
number
Alarm code
Abnormal
number
Alarm code
Abnormal
number
Alarm code
Abnormal
number
Alarm code
00 (H00)
No alarm
33 (H21)
OV2
64 (H40)
EEP
144 (H90)
OHT
16 (H10)
OC1
34 (H22)
OV3
66 (H42)
PIDE
160 (HA0)
OPT
17 (H11)
OC2
35 (H23)
OV0
97 (H61)
OLS
192 (HC0)
CPU
18 (H12)
OC3
48 (H30)
THT
98 (H62)
OL2
193 (HC1)
CPR
19 (H13)
OC0
49 (H31)
THN
179 (HB3)
SCP
194 (HC2)
EBE
32 (H20)
OV1
50 (H32)
NTC
129 (H81)
AErr
4.62 Accumulative motor operation time function (P.292, P.293)
P.292 “Accumulative motor operation time (min)”
P.293 “Accumulative motor operation time (day)”
Parameter
Factory setting
Setting range
Remarks
292
0
0~1439min
---
293
0
0~9999day
---
<Setting>
• P.292 means the minutes of accumulative motor operation, execute P.998, cut off the power,
updated value cannot change the value of P.292.Only set 0 to P.292, can clear the accumulation of
time.