90
4. Parameter description
Parameter
<Setting>
• When P.65=0, retry is invalid. When alarm occurs, the voltage output is stopped, the ‘Alarm’ lamp
is lit, and all the inverter functions are disabled.
• When P.65=1, in case ‘over-voltage between P-N’ occurs, the voltage output is stopped. After a
period of waiting time (the set value of P.68), the retry is executed.
• When P.65=2, once ‘over-current’ occurs, the voltage output is stopped. After a period of waiting
time (the set value of P.68), the retry is executed.
• When P.65=3, in case ‘over-voltage between P-N’ or ‘over-current’ occurs, the voltage output is
stopped. After a period of waiting time (the set value of P.68), the retry is executed.
• When P.65=4, retry is effective. When alarm occurs, the voltage output is stopped. After a period of
waiting time (the set value of P.68), the retry is executed.
• When P.67=0, Retry is invalid.
• When P.67
≠
0, given continuous alarm occurs for times within the pre-defined upper limit of P.67,
retries will be valid. However, once the upper limit is exceeded, the retry is valid no more.
• For each time the retry occurs, the value of P.69 will be increased by 1 automatically, so the number
of P.69 read from the memory just indicates the number of retry accumulation times.
• If P.69 is rewritten with 0, the number of retry executed is erased.
Note: The inverter will retry until the return wait time of P.68 is past. Therefore, this function is selected, the
operator may cause danger, please be careful.
4.30
Brake Selection (P.71)
P.71 “Idling braking and linear braking selection”
Parameter
factory setting
Setting range
Remarks
71
1
0~1
---
<Setting>
• When P.71=0, it is now idling braking. The output of the inverter will terminate immediately after
pressing
STOP
RESET
, and the motor will be ‘racing’
• When P.71=1, it is now beeline brake. The output of the inverter will follow the
acceleration/deceleration curve after pressing
STOP
RESET
.
4.31
Carrier frequency (P.72)
P.72 “Carrier frequency”
Parameter
Factory setting
Setting range
Remarks
72
5.0kHz
0.7~14.5kHz
---