Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
53
Setting
Default
Range
Incr.
Activate high current trip -
ground
OFF OFF,
1-5
1
The
Activate high current trip - ground
setting determines when ground high current tripping is
enabled (e.g., if
Activate high current trip - ground
= 2, then ground high current tripping is enabled
for the second [2nd] trip operation and every following trip operation).
The setting range for
Activate high current trip - ground
adjusts according to
Operations to
lockout - ground
(e.g., if
Operations to lockout - ground
= 4, then the range for
Activate high
current trip - ground
is from 1 to 4).
•
This setting is hidden and set to OFF if
High current trip - ground
is set to N.
No.
Setting
Default
Range
Incr.
31
High current lockout - phase
N
Y/N
The
High current lockout - phase
setting enables the following two settings for phase high current lockout, if
set to Y. Phase high current lockout is not affected by the cold load pickup scheme.
•
This setting is hidden and set to N if
Fast curve - phase
(No. 8) and
Delay curve - phase
(No. 10) are
both set to OFF.
Setting
Default
Range
Incr.
High current lockout - phase
OFF
OFF, 1.00-19.99 multiples of Min.
trip - phase
0.01
The
High current lockout - phase
(multiples of
Min. trip - phase
) setting determines the exceeded
phase current threshold at which the SEL-351P goes to the lockout state immediately when tripping.
Example: If
High current lockout - phase
= 13.00 (multiples of
Min. trip - phase
) and
Min. trip -
phase
(No. 5) = 200.00 Amps primary, then the phase current threshold for phase high
current lockout operates at a value equal to:
13.00
•
200.00 Amps primary = 2600.00 Amps primary
The upper limit of this setting (20.00 multiples) is calculated from the Amps secondary range upper
limit [20] and settings
CT Ratio
(No. 3) [200.0] and
Min. trip - phase
(No. 5) [200.00]:
(20
•
200.0)/200.00 = 20.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly
different than expected (e.g., 19.99 instead of 20.00).
•
This setting is hidden and set to OFF if
High current lockout - phase
is set to N.
Setting
Default
Range
Incr.
Activate high current
lockout - phase
OFF OFF,
1-5
1
The
Activate high current lockout - phase
setting determines when phase high current lockout is
enabled (e.g., if
Activate high current lockout - phase
= 3, then phase high current tripping is
enabled for the third [3rd] trip operation and every following trip operation).
The setting range for
Activate high current lockout - phase
adjusts according to
Operations to
lockout - phase
(e.g., if
Operations to lockout - phase
= 4, then the range for
Activate high current
lockout - phase
is from 1 to 4).
•
This setting is hidden and set to OFF if
High current lockout - phase
is set to N.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......