Date Code 990215
Inputs, Outputs, Timers, and Other Control Logic
7-37
SEL-351P Manual Técnico
Make corresponding, complementary text settings:
DP1_1 = 79 ENABLED
DP1_0 = 79 DISABLED
Display point setting DP1 controls the display of the text settings.
Reclosing Relay Enabled
In Figure SECTION 7: .28, optoisolated input IN102 is energized to enable the reclosing relay,
resulting in:
DP1 = IN102 = logical 1
This results in the display of corresponding text setting DP1_1 on the front-panel display:
79 ENABLED
Reclosing Relay Disabled
In Figure SECTION 7: .28, optoisolated input IN102 is deenergized to disable the reclosing
relay, resulting in:
DP1 = IN102 = logical 0
This results in the display of corresponding text setting DP1_0 on the front-panel display:
79 DISABLED
Circuit Breaker Status Indication
Make SEL
OGIC
Control Equation display point setting DP2:
DP2 = IN101
Make corresponding, complementary text settings:
DP2_1 = BREAKER CLOSED
DP2_0 = BREAKER OPEN
Display point setting DP2 controls the display of the text settings.
Circuit Breaker Closed
In Figure SECTION 7: .28, optoisolated input IN101 is energized when the 52a circuit breaker
auxiliary contact is closed, resulting in:
DP2 = IN101 = logical 1
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......