Date Code 990430
Factory-Set Logic
1-5
SEL-351P Manual Técnico
EZ Global Settings
(SHO FZ command; SET FZ command)
Corresponding “Regular” Global Settings
(SHO G command; SET G command)
System Frequency
Phase Rotation
NFREQ
PHROT
Recloser Wear Monitor (AUTO, Y, N)
Interrupt rating
EBMON
COS1, COS2, COS3
KASP1, KASP2, KASP3
Reset trip-latched LEDs when recloser closes
(Y/N)
RSTLED
True three-phase voltage connected (Y/N)
3PVOLT
Battery Amp-hours
% Battery capacity for sleep
AMPHR
SLPCAP
Turn on the 12 V power (Y/N)
Keep the 12 V power on while asleep (Y/N)
ON12V
12VSLP
SF6 low pressure warning threshold
SF6PRS
Overcurrent Element Functions Overview
When the factory default EZ settings are active for a particular settings group, many of the
overcurrent elements in that settings group have specific functions, as explained in Table 1.2.
Table SECTION 1: .2: Overcurrent Element Functions with EZ Settings Operative
Overcurrent Element
Function with EZ Settings
Operative
Associated Settings
51P1T
Fast curve - phase
51P1P, 51P1C, 51P1TD,
51P1RS, 51P1CT, 51P1MR
51G1T, 51N1T
Fast curve - ground
51G1P, 51G1C, 51G1TD,
51G1RS, 51G1CT, 51G1MR
51N1P, 51N1C, 51N1TD,
51N1RS, 51N1CT, 51N1MR
51P2T
Delay curve - phase
51P2P, 51P2C, 51P2TD,
51P2RS, 51P2CT, 51P2MR
51G2T, 51N2T
Delay curve - ground
51G2P, 51G2C, 51G2TD,
51G2RS, 51G2CT, 51G2MR
51N2P, 51N2C, 51N2TD,
51N2RS, 51N2CT, 51N2MR
67N3T
SEF element
50N3P, 67N3D
67P2T
High current trip - phase
50P2P, 67P2D
67G2T, 67N2T
High current trip - ground
50G2P, 67G2D,
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......