7-24
Inputs, Outputs, Timers, and Other Control Logic
Date Code 990215
SEL-351P Manual Técnico
Figure SECTION 7: .20:
Active Setting Group Switching (with Single Input) Time
Line
Active Setting Group Switching Example 2
Previous SEL relays (e.g., SEL-321 and SEL-251 Relays) have multiple settings groups
controlled by the assertion of three optoisolated inputs (e.g., IN101, IN102, and IN103) in
different combinations as shown in Table SECTION 7: .6.
Table SECTION 7: .6: Active Setting Group Switching Input Logic
Input States
Active
IN103 IN102 IN101
Setting
Group
0 0 0
Remote
0 0 1
Group
1
0 1 0
Group
2
0 1 1
Group
3
1 0 0
Group
4
1 0 1
Group
5
1 1 0
Group
6
The SEL-351P can be programmed to operate similarly. Use three optoisolated inputs to switch
between the six setting groups in the SEL-351P. In this example, optoisolated inputs IN101,