Settings
62
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
Setting
Default
Range
Incr.
Keep the 12 V power on
while asleep
N Y/N
Refer to the preceding
% Battery capacity for sleep
setting (No. 44).
Keep the 12 V power on while asleep
= Y:
•
If the SEL-351P goes to sleep, but the temperature-compensated battery voltage
measurement is above 80% nominal voltage, the 12 Vdc power is kept on.
•
If the temperature-compensated battery voltage measurement falls below 80% nominal
voltage during an extended outage, the 12 Vdc power is turned off.
•
The application for this feature involves keeping a radio or some device powered to receive
a signal to transmit to the WAKE-UP port to wake up the SEL-351P remotely (see the front
of
Section 10
in the
SEL-351P Manual Técnico
for more information on the WAKE-UP
port).
Keep the 12 V power on while asleep
= N:
•
If the SEL-351P goes to sleep, the 12 Vdc power is turned off.
•
This setting is hidden and set to N if
Turn on the 12 V power
is set to N.
No.
Setting
Default
Range
Incr.
46
SF6 low pressure warning
threshold
1.1 0.9-2.0
atmospheres
0.1
The SF6 gas pressure inside the GVR recloser is typically at 1.3 atmospheres (atm). If the pressure goes below
the SF6 low pressure warning threshold, then the ALARM output contact pulse for 5 seconds. The present SF6
gas pressure can be accessed with the STATUS command (see Table 2 in the
Communications
section).
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......