Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
43
Setting
Default
Range
Incr.
EM reset - phase delay
curve
N Y/N
The
EM reset - phase delay curve
setting enables the electromechanical reset emulation for the US
or IEC curve, if set to Y.
•
This
setting is usually set to N, except for special applications.
•
This setting is hidden and set to N if
Delay curve - phase
is programmed with a recloser or user
curve.
No.
Setting
Default
Range
Incr.
11
Delay curve - ground
13
OFF, U1-U5, C1-C5, recloser or
user curve
The
Delay curve - ground
setting selects the time-overcurrent curve for ground fast curve tripping. Curve
designations are provided in Table 6 and Table 7.
If
Min. trip - ground
(No. 6) is effectively set <0.1 Amp secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Min. trip - ground
[No. 6] <20.00 Amps primary), then
Delay curve - ground
flattens out above 1.5 Amps
secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Delay curve - ground
flattens out above 300 Amps primary).
•
This setting is hidden and set to OFF if
Min. trip -ground
(No. 6) is set to OFF.
•
If
Delay curve - ground
is programmed with a US (U1-U5) or IEC (C1-C5) curve, enter the following
two settings:
Setting
Default
Range
Incr.
Time-dial - ground delay
curve
1.00
0.50 - 15.00 for US curves U1-U5
0.05 - 1.00 for IEC curves C1-C5
0.01
0.01
The
Time-dial - ground delay curve
setting shifts the US or IEC curve in time by the entered
multiplier.
•
This
setting is hidden and nonoperative if
Delay curve - ground
is programmed with a recloser
or user curve.
Setting
Default
Range
Incr.
EM reset - ground delay
curve
N Y/N
The
EM reset - ground delay curve
setting enables the electromechanical reset emulation for the
US or IEC curve, if set to Y.
•
This
setting is usually set to N, except for special applications.
•
This setting is hidden and set to N if
Delay curve - ground
is programmed with a recloser or
user curve.
No.
Setting
Default
Range
Incr.
12
Time delay - SEF
0.00
0-16000.00 cycles
0.25 cyc.
The
Time delay - SEF
setting programs an intentional time delay for the definite-time SEF (sensitive earth
fault) overcurrent element. This is in addition to the built-in 2-cycle time delay.
•
This setting is hidden and set to zero (0) if
Min. trip - SEF
(No. 7) is set to OFF.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......