Settings
48
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
No.
Setting
Default
Range
Incr.
25
Complex fast curve - phase
N
Y/N
The
Complex fast curve - phase
setting enables the following three settings for the phase fast curve, if set to
Y.
•
This setting is hidden and set to N if
Fast curve - phase
(No. 8) is set to OFF.
Setting
Default
Range
Incr.
Const. time adder - phase
fast curve
0.00
0-60.00 cycles
0.25 cyc.
The
Const. time adder - phase fast curve
setting adds a constant time to the phase fast curve, if set
to other than 0 cycles.
•
This setting is hidden and set to zero (0) if
Complex fast curve - phase
is set to N.
Setting
Default
Range
Incr.
Vert. multiplier - phase fast
curve
1.00
0.10 - 2.00
0.01
The
Vert. multiplier - phase fast curve
setting shifts the phase fast curve in time, by the entered
multiplier, if
Fast curve - phase
(No. 8) is programmed with a recloser or user curve. If no particular
multiplier is desired, set
Vert. multiplier - phase fast curve
equal to 1.00.
•
If
Fast curve - phase
(No. 8) is programmed with a US (U1-U5) or IEC (C1-C5) curve,
Vert.
multiplier - phase fast curve
is hidden and nonoperative. The preceding
Time-dial - phase fast
curve
(No. 8) subsetting provides the US and IEC curves with an effective vertical multiplier,
instead.
•
This setting has no multiplying effect on the
Constant time adder - phase fast curve
and
Min.
response time - phase fast curve
settings. They all operate independently.
•
This setting is hidden and set to 1.00 if
Complex fast curve - phase
is set to N and
Fast
curve-phase
(No. 8) is programmed with a recloser or user curve.
Setting
Default
Range
Incr.
Min. response - phase fast
curve
0.00
0-60.00 cycles
0.25 cyc.
The phase fast curve can trip no faster than the
Min. response time - phase fast curve
setting.
If the
Min. response time - phase fast curve
setting is set equal to zero (0), it has no effect on the
phase fast curve. If the
Min. response time - phase fast curve
setting is set equal to 15 cycles, for
example, the phase fast curve cannot trip on the portion of the curve that is faster than 15 cycles - the
phase fast curve effectively flattens out at 15 cycles.
•
This setting is hidden and set to zero (0) if
Complex fast curve - phase
is set to N.
No.
Setting
Default
Range
Incr.
26
Complex fast curve - ground
N
Y/N
The
Complex fast curve - ground
setting enables the following three settings for the ground fast curve, if set
to Y.
•
This setting is hidden and set to N if
Fast curve - ground
(No. 9) is set to OFF.
Setting
Default
Range
Incr.
Const. time adder - ground
fast curve
0.00
0-60.00 cycles
0.25 cyc.
The
Const. time adder - ground fast curve
setting adds a constant time to the ground fast curve, if
set to other than 0 cycles.
•
This setting is hidden and set to zero (0) if
Complex fast curve - ground
is set to N.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......