Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
51
Setting
Default
Range
Incr.
Vert. multiplier - ground
delay curve
1.00
0.10 - 2.00
0.01
The
Vert. multiplier - ground delay curve
setting shifts the phase delay curve in time, by the entered
multiplier, if
Delay curve - ground
(No. 11) is programmed with a recloser or user curve. If no
particular multiplier is desired, set
Vert. multiplier - ground delay curve
equal to 1.00.
•
If
Delay curve - ground
(No. 11) is programmed with a US (U1-U5) or IEC (C1-C5) curve,
Vert. multiplier - ground delay curve
is hidden and nonoperative. The preceding
Time-dial -
ground delay curve
(No. 11) - setting provides the US and IEC curves with an effective vertical
multiplier, instead.
•
This setting has no multiplying effect on the
Constant time adder - ground delay curve
and
Min. response time - ground delay curve
settings. They all operate independently.
•
This setting is hidden and set to 1.00 if
Complex delay curve - ground
is set to N and
Delay
curve - ground
(No. 11) is programmed with a recloser or user curve.
Setting
Default
Range
Incr.
Min. response - ground
delay curve
0.00
0-60.00 cycles
0.25 cyc.
The ground delay curve can trip no faster than the
Min. response time - ground delay curve
setting.
If the
Min. response time - ground delay curve
setting is set equal to zero (0), it has no effect on
the ground delay curve. If the
Min. response time - ground delay curve
setting is set equal to
15 cycles, for example, the ground delay curve cannot trip on the portion of the curve that is faster than
15 cycles - the ground delay curve effectively flattens out at 15 cycles.
•
This setting is hidden and set to zero (0) if
Complex delay curve - ground
is set to N.
No.
Setting
Default
Range
Incr.
29 High
current
trip - phase
N
Y/N
The
High current trip - phase
setting enables the following three settings for phase high current tripping, if
set to Y. Phase high current tripping is not affected by the cold load pickup scheme.
•
This setting is hidden and set to N if
Fast curve - phase
(No. 8) and
Delay curve - phase
(No. 10) are
both set to OFF.
Setting
Default
Range
Incr.
High current trip - phase
OFF
OFF, 1.00-19.99 multiples of Min.
trip - phase
0.01
The
High current trip - phase
(multiples of
Min. trip - phase
) setting determines the phase current
threshold for phase high current tripping.
Example: If
High current trip - phase
= 12.00 (multiples of
Min. trip - phase
) and
Min. trip -
phase
(No. 5) = 200.00 Amps primary, then the phase current threshold for phase high
current tripping operates at a value equal to:
12.00
•
200.00 Amps primary = 2400.00 Amps primary
The upper limit of this setting (20.00 multiples) is calculated from the Amps secondary range upper
limit [20] and settings
CT Ratio
(No. 3) [200.0] and
Min. trip - phase
(No. 5) [200.00]:
(20
•
200.0)/200.00 = 20.00 multiples (upper limit)
Due to processor calculations and rounding techniques, displayed range numbers may appear slightly
different than expected (e.g., 19.99 instead of 20.00).
•
This setting is hidden and set to OFF if
High current trip - phase
is set to N.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......