Date Code 990430
Setting the SEL-351P Recloser Control
9-3
SEL
-
351P Manual Técnico
The SEL-351P checks each entry to ensure that it is within the setting range. If it is not, an “Out
of Range” message is generated, and the control prompts for the setting again.
When all the settings are entered, the control displays the new settings and prompts for approval
to enable them. Answer
Y<ENTER>
to enable the new settings. If changes are made to Global,
EZ Global, SER, Text, or Port settings (see Table SECTION 9: .1), the SEL-351P is disabled
while it saves the new settings. If changes are made to the EZ Recloser Control, Group, or Logic
settings for the active setting group (see Table SECTION 9: .1), the SEL-351P is disabled while
it saves the new settings. The ALARM contact closes momentarily for “b” contact (opens for an
“a”; see Figure 7.26), and the CONTROL ENABLED LED extinguishes while the control is
disabled. The SEL-351P is disabled for about 1 second. If Logic settings are changed for the
active group, the SEL-351P can be disabled for up to 15 seconds.
If changes are made to the EZ Recloser Control, Group, or Logic settings for a setting group
other than the active setting group (see Table SECTION 9: .1), the SEL-351P is not disabled
while it saves the new settings. The ALARM contact closes momentarily for “b” contact (opens
for an “a”; see Figure 7.26), but the CONTROL ENABLED LED remains on while the new
settings are saved.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......