S
ETTINGS
S
HEET
Page
8
of 23
F
OR THE
SEL-351P R
ECLOSER
C
ONTROL
Date
G
ROUP
S
ETTINGS
(S
ERIAL
P
ORT
C
OMMAND
SET
AND
F
RONT
P
ANEL
)
Date Code 990215
Synchronism Check Elements (see Figures 3.24 and 3.25)
(Make the following settings if preceding enable setting E25 = Y)
Voltage window - low threshold (0.0-150.0 V secondary)
25VLO =
Voltage window - high threshold (0.0-150.0 V secondary)
25VHI =
Maximum slip frequency (0.005-0.500 Hz)
25SF =
Maximum angle 1 (0
°
-80
°
in 1-degree steps)
25ANG1 =
Maximum angle 2 (0
°
-80
°
in 1-degree steps)
25ANG2 =
Synchronizing phase (VA, VB, VC)
SYNCP =
Breaker close time for angle compensation (0.00-60.00 cycles in
0.25-cycle steps)
TCLOSD=
Frequency Element (see Figures 3.27 and 3.28)
(Make the following settings if preceding enable setting E81 = Y)
Phase undervoltage block (20.0-150.0 V secondary)
27B81P =
Level 1 pickup (OFF, 40.10-65.00 Hz)
81D1P =
Level 1 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D1D =
Level 2 pickup (OFF, 40.10-65.00 Hz)
81D2P =
Level 2 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D2D =
Level 3 pickup (OFF, 40.10-65.00 Hz)
81D3P =
Level 3 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D3D =
Level 4 pickup (OFF, 40.10-65.00 Hz)
81D4P =
Level 4 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D4D =
Level 5 pickup (OFF, 40.10-65.00 Hz)
81D5P =
Level 5 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D5D =
Level 6 pickup (OFF, 40.10-65.00 Hz)
81D6P =
Level 6 time delay (2.00-16000.00 cycles in 0.25-cycle steps)
81D6D =
Reclosing Relay (see Tables 6.2 and 6.3)
(Make the following settings if preceding enable setting E79 = Y; open
intervals should not be set to less than 30 cycles, otherwise the control
will go to lockout prematurely)
Open interval 1 time (0.00-999999.00 cycles in 0.25-cycle steps)
79OI1 =
Open interval 2 time (0.00-999999.00 cycles in 0.25-cycle steps)
79OI2 =
Open interval 3 time (0.00-999999.00 cycles in 0.25-cycle steps)
79OI3 =
Open interval 4 time (0.00-999999.00 cycles in 0.25-cycle steps)
79OI4 =
Reset time from reclose cycle (0.00-999999.00 cycles in 0.25-cycle
steps)
79RSD =
Reset time from lockout (0.00-999999.00 cycles in 0.25-cycle steps)
79RSLD =
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......