Date Code 990215
Close and Reclose Logic
6-11
SEL-351P Manual Técnico
In the above referenced subsection
Synchronism Check Elements
, note item 3 under
Synchronism Check Element Outputs, Voltages V
P
and V
S
are “Slipping.”
Item 3 describes a
last attempt for a synchronism check reclose before timer 79CLSD times out (or setting 79CLSD
= 0.00 and only one check is made).
R
ECLOSING
R
ELAY
Note that input:
Reclosing Relay Open Interval Time-Out
in Figure SECTION 6: .2 is the logic input that is qualified by SEL
OGIC
Control Equation
setting 79CLS, and then propagated on to the close logic in Figure SECTION 6: .1 to
automatically reclose a circuit breaker. The explanation that follows in this reclosing relay
subsection describes all the reclosing relay settings and logic that eventually result in this open
interval time-out logic input into Figure SECTION 6: .2. Other aspects of the reclosing relay are
also explained. Up to four (4) automatic reclosures (shots) are available.
The reclose enable setting, E79, has setting choices N, 1, 2, 3, and 4. Setting E79 = N defeats the
reclosing relay. Setting choices 1 through 4 are the number of desired automatic reclosures (see
Open Interval Timers
that follows in this subsection).
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......