12-26
Standard Event Reports and SER
Date Code 990215
SEL-351P Manual Técnico
E
XAMPLE
S
TANDARD
15-C
YCLE
E
VENT
R
EPORT
The following example standard 15-cycle event report in Figure SECTION 12: .2 also
corresponds to the example sequential events recorder (SER) report in Figure SECTION 12: .5.
The circled numbers in Figure SECTION 12: .2 correspond to the SER row numbers in Figure
SECTION 12: .5. The row explanations follow Figure SECTION 12: .5.
In Figure SECTION 12: .2, the arrow (>) in the column following the
Freq
column identifies the
“trigger” row. This is the row that corresponds to the Date and Time values at the top of the
event report.
The asterisk (*) in the column following the
Freq
column identifies the row with the maximum
phase current. The maximum phase current is calculated from the row identified with the
asterisk and the row one quarter-cycle previous (see Figure SECTION 12: .3 and Figure
SECTION 12: .4). These currents are listed at the end of the event report in the event summary.
If the “trigger” row (>) and the maximum phase current row (*) are the same row, the * symbol
takes precedence.
=+>eve
RECLOSER R1 Date: 06/01/98 Time: 12:23:52.527
FEEDER 2101
FID=SEL-351P-R100-V0-D990213 CID=C867 BCBFID=R103
Out In 55CS
Currents (Amps Pri) Voltages (kV Pri) 1357TB 135 22hF
IA IB IC IG VA VB VC VS Freq 246ACr 246 ABg6
[1]
120 -152 29 -3 3.3 -6.7 3.4 -0.0 60.01 ...... ... *.b.
104 53 -158 -1 5.9 -0.1 -5.8 0.0 60.01 ...... ... *.b.
-122 150 -30 -2 -3.3 6.7 -3.4 -0.0 60.01 ...... ... *.b.
-105 -55 157 -3 -5.9 0.1 5.8 0.0 60.01 ...... ... *.b.
[2]
121 -151 29 -1 3.3 -6.7 3.4 0.0 60.01 ...... ... *.b.
104 54 -158 0 5.9 -0.1 -5.8 0.0 60.01 ...... ... *.b.
-122 151 -30 -1 -3.3 6.7 -3.4 0.0 60.01 ...... ... *.b.
-105 -55 157 -3 -5.9 0.1 5.8 0.0 60.01 ...... ... *.b.
[3]
122 -152 29 -1 3.3 -6.7 3.4 -0.0 60.01 ...... ... *.b.
104 53 -158 -1 5.8 -0.1 -5.8 -0.0 60.01 ...... ... *.b.
-123 151 -30 -2 -3.3 6.7 -3.4 0.0 60.01 ...... ... *.b.
-105 -54 157 -2 -5.8 0.1 5.8 0.0 60.01 ...... ... *.b.
[4]
121 -152 29 -2 3.3 -6.7 3.4 -0.0 60.01 ...... ... *.b.
190 54 -158 86 4.4 -0.6 -6.3 0.0 60.01 ...... ... *.b.
146 150 -29 267 -2.5 7.0 -3.1 0.0 60.01 ...... ... *.b.
-551 -55 157 -449 -2.1 1.5 7.2 0.0 60.01>....T. ... *.b.
[5]
-484 -151 28 -607 1.3 -7.6 2.5 -0.0 60.01 ....T. ... *.b.
824 54 -158 720 1.2 -1.9 -7.5 0.0 60.01 ....T. ... *.b.
549 150 -29 670 -0.8 7.8 -2.3 0.0 60.01 ....T. ... *.b.
-825 -55 157 -723 -1.2 1.9 7.5 0.0 60.01 ....T. ... *.b.
-550 -151 28 -673 0.8 -7.8 2.3 -0.0 60.01*....T. ... *.b.
824 55 -158 721 1.2 -1.8 -7.5 0.0 60.01 ....T. ... *.b.
548 150 -29 669 -0.8 7.8 -2.3 0.0 60.01 ....T. ... *.b.
-826 -56 157 -725 -1.2 1.8 7.5 -0.0 60.01 ....T. ... *.b.
[7]
-548 -151 28 -671 0.8 -7.8 2.3 0.0 60.07 ....T. ... *.b.
see Figure 12.1
firmware identifier
firmware checksum
identifier
Battery charger/power
supply board
identifier
one cycle of data
11
see Figure 12.3 and
Figure 12.4 for
details on this
example one cycle
of phase A (channel
IA) current
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......