Settings
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
61
No.
Setting
Default
Range
Incr.
41
Reset trip-latched LEDs
when recloser closes
Y Y/N
Figure 8 shows the front-panel trip-latched LEDs. They are: TRIP, CURVA RÁPIDA, ALTA CORRENTE,
RELÉ FREQ., and all TIPO DE FALTA LEDs.
These LEDs latch in at the rising edge of trip and remain illuminated - even after power is turned off and then
on again.
Reset trip-latched LEDs when recloser closes
= Y:
The trip-latched LEDs extinguish automatically when the recloser closes.
Reset trip-latched LEDs when recloser closes
= N:
The trip-latched LEDs extinguish automatically (or are newly latched in) when the SEL-351P trips again.
No.
Setting
Default
Range
Incr.
42
True three-phase voltage
connected
N Y/N
If
True three-phase voltage
is connected to the SEL-351P, the indication provided by A, B, and C TIPO
DE FALTA LEDs is made more secure (see Figure 8).
No.
Setting
Default
Range
Incr.
43
Battery Amp-hours
8.0
6.5-20.0 Amp-hours
0.1
This is the amp-hour rating of the 24 Vdc battery system connected to pins 6 [+] and 2 [-] on POWER
connector J6.
No.
Setting
Default
Range
Incr.
44
% Battery capacity for sleep
20
0-100%
1
The
% Battery capacity for sleep
setting is typically set at 20% capacity, so that the battery is not totally
depleted during an extended outage.
•
If the
% Battery capacity for sleep
setting (e.g., 20% capacity) is reached or the temperature-
compensated battery voltage measurement falls below 80% nominal voltage during an extended outage,
the SEL-351P goes to sleep, unless communications are actively ongoing with the SEL-351P.
•
If the
% Battery capacity for sleep
is set at 0% capacity and the SEL-351P is operating on the battery
during an extended outage, the SEL-351P goes to sleep when the temperature-compensated battery
voltage measurement falls below 80% nominal voltage, unless communications are actively ongoing with
the SEL-351P.
•
If the temperature-compensated battery voltage measurement falls below 70% nominal voltage during an
extended outage, the SEL-351P goes to sleep, regardless of any other conditions.
No.
Setting
Default
Range
Incr.
45
Turn on the 12 V power
N
Y/N
The
Turn on the 12 V power
setting turns the 12 V power on when set to Y.
•
See Figure 9 and Table 1 for information on how to access the 12 Vdc power and its capability rating.
•
If the
Turn on the 12 V power
setting is set to Y, then you are prompted to enter the following setting:
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......