Date Code 990430
Breaker/Recloser Monitor, Battery System Monitor,
8-1
Metering, and Load Profile Functions
SEL-351P Manual Técnico
SECTION 8: BREAKER/RECLOSER MONITOR, BATTERY
SYSTEM MONITOR, METERING, AND LOAD
PROFILE FUNCTIONS
I
NTRODUCTION
The SEL-351P Recloser Control monitoring functions include:
•
Breaker/Recloser Contact Wear Monitor
•
Battery System Monitor
In addition to instantaneous metering, the SEL-351P metering functions include:
•
Demand Metering
•
Energy Metering
•
Maximum/Minimum Metering
This section explains these functions in detail.
B
REAKER
/R
ECLOSER
C
ONTACT
W
EAR
M
ONITOR
The breaker/recloser contact wear monitor in the SEL-351P provides information that helps in
scheduling circuit breaker or recloser maintenance. This monitoring function accumulates the
number of internal and external trip operations and integrates the number of close-open
operations and the per-phase current during each opening operation. The SEL-351P compares
the integrated close-open information to a pre-defined breaker or recloser maintenance curve to
calculate the percent contact wear on a per-pole basis. The SEL-351P updates and stores the
contact wear information, and the number of trip operations, in non-volatile memory. You can
view this information through the front-panel display and by communicating with the SEL-351P
through any serial communication port with a computer.
Individual phase Breaker Contact Wear bits, BCWA, BCWB, and BCWC, assert when the
contact wear percentage on their respective phases reaches 100%. You can use these individual
phase elements or the combined result of these elements, BCW (asserts when BCWA or BCWB
or BCWC assert), in a SEL
OGIC
®
Control Equation to alarm or control other functions, such as
block reclosing.
Enable the breaker/recloser contact wear monitor with the global EZ setting
Recloser Wear
Monitor (AUTO, Y, N)
. Access this setting with the SET FZ (global EZ settings) command from
Access Level E (EZ) or Access Level 2. The contact wear monitor is configured as follows:
•
Recloser Wear Monitor (AUTO, Y, N)
= N
disables the contact wear monitor. Setting
EBMON in Table SECTION 8: .1 is automatically set EBMON = N and the rest of the
settings in Table SECTION 8: .1 are hidden.
•
Recloser Wear Monitor (AUTO, Y, N)
= Y
enables the contact wear monitor. Setting
EBMON in Table SECTION 8: .1 is automatically set EBMON = Y, but you must then
use the
SET G
command (global settings) in Access Level 2 to enter the rest of the
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......