Date Code 990215
Factory-Set Logic
1-55
SEL-351P Manual Técnico
For example, Trip latch LED17 (Y/N) = Y and LED17 = 81D1T
The RELÉ FREQ. (underfrequency trip) LED illuminates when Relay Word bit 81D1T
is asserted to logical 1 and a rising-edge of TRIP occurs.
Trip-latched LEDs (e.g., the RELÉ FREQ. [underfrequency trip] LED) remain latched in and
illuminated until one of the following occur:
•
Next trip occurs
•
TARGET RESET pushbutton is pressed
•
Recloser closes [if global setting “Reset trip-latched LEDs when recloser closes
(Y/N)” = Y]
CONTROLE
HABILITADO
FONTE
CA
BATERIA
PROBLEMA
LINHA
VIVA
LED11L = N
LED11 = 59A1
SEL
OGIC
Setting:
Trip Latch
LED (Y/N)?
LED12L = N
LED12 = NOBATT
+!BCBOK+DTFAIL
LED13 = !LT7
(always extinguished from
factory - see Figure 1.47)
LED13L = N
DWG: MP351P035
Fixed-Function
LED
Figure SECTION 1: .45:
Front-Panel Status LEDs
Figure 2.1 through Figure 2.4 and associated text in subsection
Voltage Connections
in
Section 2: Additional Installation Details
discuss possible changes necessary to the factory
default AC SUPPLY LED SEL
OGIC
Control Equations setting LED11, for various voltage
connections.
TRIP
CURVA
RÁPIDA
ALTA
CORRENTE
RELÉ
FREQ.
LED14L = Y
LED14 = TRIP
SEL
OGIC
Setting:
Trip Latch
LED (Y/N)?
LED15L = Y
LED15 = 51P1T
+51G1T+51N1T
LED17 = 81D1T
LED17L = Y
DWG: MP351P036
LED16L = Y
LED16 = 67P2T
+67G2T+67N2T
Figure SECTION 1: .46:
Front-Panel Trip Target LEDs
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......