Settings
44
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
No.
Setting
Default
Range
Incr.
13
Operations - phase fast
curve
2 OFF,
1-5
1
The
Operations - phase fast curve
setting determines the number of phase fast curve trip operations (e.g.,
if
Operations - phase fast curve
= 2, then the phase fast curve is enabled for the first two [2] trip
operations).
•
This setting is hidden and set to OFF if
Fast curve - phase
(No. 8) is set to OFF.
•
This setting only enables the phase fast curve operations; it does not disable the phase delay curve (the
phase delay curve is always active). Traditional protection schemes use fast curves followed by delay
curves so the delay curves do not have to be defeated. If a slower first operation than second operation
is desired, higher logic level settings changes are required
.
No.
Setting
Default
Range
Incr.
14
Operations - ground fast
curve
2 OFF,
1-5
1
The
Operations - ground fast curve
setting determines the number of ground fast curve trip operations
(e.g., if
Operations - ground fast curve
= 2, then the ground fast curve is enabled for the first two [2] trip
operations).
•
This setting is hidden and set to OFF if
Fast curve - ground
(No. 9) is set to OFF.
•
This setting only enables the ground fast curve operations; it does not disable the ground delay curve
(the ground delay curve is always active, provided that the TERRA HABILITADO operator control is
on). Traditional protection schemes use fast curves followed by delay curves so the delay curves do not
have to be defeated. If a slower first operation than second operation is desired, higher logic level
settings changes are required.
No.
Setting
Default
Range
Incr.
15
Operations to lockout -
phase
4 OFF,
1-5
1
The
Operations to lockout - phase
setting determines the total number of phase curve trip operations. The
difference between setting
Operations to lockout - phase
and setting
Operations - phase fast curve
(No. 13)
is the number of remaining phase delay curve operations (e.g., 4 - 2 = 2).
The setting range for
Operations to lockout - phase
adjusts according to
Operations - phase fast curve
(e.g., if
Operations - phase fast curve
= 2, then the range for
Operations to lockout - phase
is from 2 to 5).
•
If
Delay curve - phase
(No. 10) = OFF, then
Operations to lockout - phase
is set automatically equal to
Operations - phase fast curve
, and there are no phase delay curve operations (e.g., 2 - 2 = 0).
•
This setting is hidden and set to OFF if
Min. trip - phase
(No. 5) is set to OFF.
•
WARNING: If
Operations to lockout - phase
(No. 15),
Operations to lockout - ground
(No. 16), and
Operations to lockout - SEF
(No. 17) are all set to OFF, then overcurrent protection and reclosing are
disabled.
However, if both
Min. trip - phase
(No. 5) and
Delay curve - phase
(No. 10) are set to values other than
OFF, the phase delay curve element is still active. If absolutely no phase protection is desired (e.g.,
“switch” mode),
Min. trip - phase
(No. 5) or
Delay curve - phase
(No. 10) must also be set to OFF.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......