Installation
10
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
CONTROL Connector J5 Details
Refer to Figure 4. Figure 4 shows greater detail on what is connected to
either side of CONTROL connector J5.
24 Vdc Whetting Voltage
The nominal 24 Vdc whetting voltage from terminals 1 and 9 can vary
from 20 to 42 Vdc. If 24 Vdc-rated optoisolated inputs (inputs IN101
through IN106) are wetted with the nominal 24 Vdc whetting voltage,
the inputs can handle the possible upper voltage output (i.e., 42 Vdc).
These inputs will be “on” at this upper limit.
The 24 Vdc voltage also whets the 52a and 52b breaker auxiliary
contacts, which are connected through terminals 5 and 13, respectively.
!
WARNING:
No grounds can be installed on the circuits connected to the 24 Vdc whetting voltage. This
voltage source is grounded inside the SEL-351P.
Capacitor Voltage Monitor and Charger Control
Terminals 6 and 14 monitor trip and close capacitor voltages,
respectively.
Terminal 6 indicates when the trip capacitor is fully charged (> 80 V).
The presumption is if the trip capacitor is fully charged to > 80 V, the
close capacitor is, likewise, fully charged.
Terminal 14 indicates when the close capacitor is charged to at least 20
V. Exceeding this 20 V threshold causes the capacitor charger control
output (terminals 10 and 2) to go below 24 Vdc (it is nominally 40 Vdc).
This low output signal to the external capacitor charger causes the
charger to go to a higher charge rate to quickly charge the capacitors to
90 V.
Capacitor Charger Power
A 20 to 40 Vdc range output on terminals 16 and 9 provides power to the
external capacitor charger.
Trip and Close Output Contacts
Terminals 7 and 15 trip and close the recloser, respectively, by
energizing a magnetic actuator in one direction or the other. The trip
and close output contacts are form c contacts, shown in their de-
energized state.
When the SEL-351P trips the recloser, the trip output contact moves to
the position to connect the trip capacitor (terminal 6) to the magnetic
Connect Battery and Charge
Capacitors for Auto-
Reclosing
Factory-default settings require
that the 24 Vdc battery be
connected and healthy and the
trip and close capacitors be
fully charged in order for auto-
reclosing to proceed after a
reclose interval times out.
Fuse the 24 Vdc
Whetting Voltage:
Read Note1 in Figure 4.
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......