Settings
34
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
S
ETTINGS
This section details the EZ (“easy”) settings – the settings used to
perform traditional recloser control operations.
Topics covered in this section:
•
Curve Designations
•
EZ (“Easy”) Settings
•
Global EZ Settings
•
EZ Settings Sheets (end of
Settings
section)
Curve Information
Fast and delay curves are available for phase and ground overcurrent
protection. These curves can be set with any of the numerous resident
curve choices:
•
Recloser Curves (see Table 6)
•
US Curves (see Table 7)
•
IEC Curves (see Table 7)
•
User-Programmable Curves (see Table 7)
The recloser curves in Table 6 show both the older electronic control
designation and the newer microprocessor-based control designation.
The recloser curves can be specified in a curve setting using either
designation. For example, a given traditional recloser curve has the
following two designations:
Older electronic control designation:
A
Newer microprocessor-based control designation: 101
Traditional recloser curve A and curve 101 are the same curve – use
either designation in making curve settings in the SEL-351P.
Important:
This
Quick-Start Installation
and User's Guide
provides only
information applicable to the EZ
settings - settings associated
with traditional recloser control
operations.
High Current Options
Available for Phase and
Ground:
•
High Current Trip
•
High Current Lockout
Curve Modifiers Available
for Any Curve Type:
•
Constant Time Adder
•
Vert. Multiplier/Time Dial
•
Min. Response Time
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......