Date Code 990215
Factory-Set Logic
1-9
SEL-351P Manual Técnico
Actively Engage Cold Load Pickup Scheme (Phase Elements Example)
SV6T propagates into Figure SECTION 1: .2 and seals in with SEL
OGIC
setting/Relay Word bit
SV8, if Relay Word bit CLP = logical 1 (EZ setting Cold load pickup-phase
≠
OFF). This
actively engages the cold load pickup scheme for the phase overcurrent elements (Relay Word bit
SV8 = logical 1).
SV7PU (=900 cycles from factory) is the
qualifiying time for cold load pickup phase
current below normal Min. trip - phase
SV8
(cold load
pickup
scheme
actively
engaged
for phase
elements)
SV7
PU
0
Loss of load diversity
Restore min. trips
Restore min. trips
scheme enabled for
phase elements
Cold load pickup scheme enabled
for phase elements
Phase current above
normal Min. trip - phase
Cold load pickup phase
current below normal
Min. trip - phase
SV7
SV7T
Relay
Word
Bits
SV6T
SV5T
RPP
CLP
50P6
52A
Recloser closed
DWG: M351R030
SEL
OGIC
Setting
Relay
Word
Bit
SEL
OGIC
Setting
and
Relay
Word
Bit
Figure SECTION 1: .2:
Cold Load Pickup Scheme Seal-in Logic for Phase
Overcurrent Elements
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......