Settings
40
SEL-351P Quick-Start Installation and User's Guide (Portuguese)
No.
Setting
Default
Range
Incr.
5
Min. trip - phase
200.00
OFF, 20.00-639.99 Amps primary
0.01
The
Min. trip - phase
setting determines the minimum phase current threshold for overcurrent detection in
primary amps.
The displayed Amps primary setting range for
Min. trip - phase
is calculated by multiplying the effective
Amps secondary range [0.10 to 3.20] by the
CT Ratio
(No. 3) [200.0]:
(0.10 to 3.20)
•
200.0 = 20.00 to 640.00 range (Amps primary)
If the
CT Ratio
setting changes, the displayed Amps primary setting range for
Min. trip - phase
changes
accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear
slightly different than expected (e.g., 639.99 instead of 640.00).
•
WARNING: If
Min. trip - phase
(No. 5)
, Min. trip - ground
(No. 6),
and
Min. trip - SEF
(No. 7)
are all set to OFF, then overcurrent protection and reclosing are disabled.
•
WARNING: If
Min. trip - phase
is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - phase
(No. 8)
Delay curve - phase
(No. 10)
Operations - phase fast curve
(No. 13)
Operations to lockout - phase
(No. 15)
Complex fast curve - phase
(No. 25)
Complex delay curve - phase
(No. 27)
High current trip - phase
(No. 29)
High current lockout - phase
(No. 31)
No.
Setting
Default
Range
Incr.
6
Min. trip - ground
50.00
OFF, 1.00-639.99 Amps primary
0.01
The
Min. trip - ground
setting determines the minimum ground current threshold for overcurrent detection
in primary amps.
The displayed Amps primary setting range for
Min. trip - ground
is calculated by multiplying the effective
Amps secondary range [0.005 to 3.20] by the
CT Ratio
(No. 3) [200.0]:
(0.005 to 3.20)
•
200.0 = 1.00 to 640.00 range (Amps primary)
If the
CT Ratio
setting changes, the displayed Amps primary setting range for
Min. trip - ground
changes
accordingly. Due to processor calculations and rounding techniques, displayed range numbers may appear
slightly different than expected (e.g., 639.99 instead of 640.00).
If
Min. trip - ground
is effectively set <0.1 Amp secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Min. trip -
ground
<20.00 Amps primary), then the corresponding curves flatten out above 1.5 Amps secondary (e.g., for
CT ratio
[No. 3] = 200.0,
Fast curve - ground
[No. 9] and
Delay curve - ground
[No. 11] flatten out above
300 Amps primary).
•
WARNING: If
Min. trip - phase
(No. 5)
, Min. trip - ground
(No. 6),
and
Min. trip - SEF
(No. 7)
are all set to OFF, then overcurrent protection and reclosing are disabled.
•
WARNING: If
Min. trip - ground
is set to OFF, then the following settings are all hidden and set to
OFF or N:
Fast curve - ground
(No. 9)
Delay curve - ground
(No. 11)
Operations - ground fast curve
(No. 14)
Operations to lockout - ground
(No. 16)
Complex fast curve - ground
(No. 26)
Complex delay curve - ground
(No. 28)
High current trip - ground
(No. 30)
High current lockout - ground
(No. 32)
Summary of Contents for SEL-351P
Page 6: ......
Page 92: ......
Page 96: ......
Page 154: ......
Page 156: ......
Page 222: ......
Page 258: ......
Page 262: ......
Page 324: ......
Page 368: ......
Page 406: ......
Page 482: ......
Page 534: ......
Page 539: ......
Page 549: ......
Page 551: ......
Page 587: ......
Page 597: ......
Page 601: ......
Page 603: ......
Page 609: ......
Page 621: ......
Page 635: ......
Page 649: ......
Page 665: ......
Page 671: ......