1. OUTLINE
IMR01N12-E7
4
1.3 Input/Output
Functions
This section describes the input/output functions of the instrument. To learn how to set each function, refer to the
respective page.
INPUT
In addition to measured input, 2 optional input functions are available.
Measured input:
Input 1 can be used for pressure sensor input or voltage/current input.
(Specify
when
ordering)
Input 2 can be used for temperature input or voltage/current input. (Specify when ordering)
Input 1
Pressure sensor input Resin pressure sensor (0.0 to 250.0 MPa)
Input 2
Thermocouple *
K
、
J
、
T
、
S
、
R
、
E
、
B
、
PLII
、
N
、
W5Re/W26Re
RTD *
Pt100
、
JPt100
[Factory set value: Pt100]
Input 1
Input 2
Voltage (low) *
0 to 100 mV DC, 0 to 10 mV DC, 0 to 1 V DC,
10 mV DC,
100 mV DC
[Factory set value: 0 to 1 V DC]
Voltage (High) *
0 to 5 V DC, 1 to 5 V DC, DC 0 to 10 V DC,
1 V DC,
5 V DC,
10 V DC
[Factory set value: 1 to 5 V DC]
Current *
0 to 20 mA DC, 4 to 20 mA DC
[Factory set value: 4 to 20 mA DC]
*
To change the input type, refer to
8. ENGINEERING MODE. (P. 50)
The second measured input can be used as non-isolated remote input.
Event input:
Optional Event input hardware is necessary. (Specify when ordering)
Event input can be used for the following functions. (Refer to P. 73.)
Memory area selection (Number of areas: 1 to 16 or 1 to 8),
Operation mode transfer (RUN/STOP, Remote/Local, Auto/Manual.),
Hold reset, Interlock release,
Manual output up/down (Motor RPM up/down), Manual output 0 % reset (Motor RPM reset)
Remote input (non-isolated type):
Remote input is to change a control setpoint by using current or voltage input from an
external device.
Remote input is available with Input 2. (Specify when ordering)
Any one of the following input types can be selected. (Refer to P. 66.)
Voltage (low)
0 to 100 mV DC, 0 to 10 mV DC, 0 to 1 V DC,
10 mV DC,
100 mV DC
Voltage (High)
0 to 5 V DC, 1 to 5 V DC, DC 0 to 10 V DC,
1 V DC,
5 V DC,
10 V DC
Current
0 to 20 mA DC, 4 to 20 mA DC