9. OPERATION
IMR01N12-E7
116
9.9 Ramp/Soak Control
Ramp/Soak control is possible by using Area soak time, Link area number and Setting change rate limiter
(up/down) in Parameter setting mode (P. 31). The operating procedure is described in the following.
1.
Press the SET key several times at Parameter setting mode
until Input 1_setting change rate limiter (up) setting screen
is displayed.
2.
Press the UP key to change the number to 5.0.
3.
Press the SET key to store the new value. The display goes
to the next parameter. Check that this screen is set to OFF.
4.
Press the SET key until Area soak time setting screen is
displayed.
5.
Press the shift key to high-light the most significant digit.
6.
Press the UP key to change the number to 6.
7.
Press the SET key to store the new value. The display goes
to the next parameter.
8.
Press the UP key to change the number to 2.
Continued on the next page.
AREA
AREA
AREA
Factory set value:
0.00.00 (0 min.00.00 sec)
AREA
Step 1:
Set the Setting change rate limiter, Area soak time and Link
area number to each of Memory area 1, 2 and 3.
AREA
AREA
Factory set value:
OFF (Unused)
Memory area No. 1
The following is based on assumptions described below.
1-Input controller (measured input: 1 point)
Present operating condition: Control STOP
Control area before operation start: Memory area 1
Setting of operation related parameters:
All parameters other than the following items have
been set to each of Memory areas 1, 2 and 3.
SV, Setting change rate limiter, Area soak time,
and Link area number
Area 1
Area 2
Area 3
Set value (SV)
150.0
C 200.0
C 50.0
C
Setting change rate limiter (up) (a, b) 5.0 MPa/min. 5.0 MPa/min.
OFF
Setting change rate limiter (down) (c)
OFF
OFF
3.0 MPa/min.
Area soak time
6 min.
6 min.
9 min. *
Link area number
2
3
OFF
Example: Ramp/Soak control by linking Memory area 1 to 3
SV2 (200.0 MPa)
SV1 (150.0 MPa)
SV3 (50.0 MPa)
30.0 MPa
(Example pressure)
Memory area 1
Memory area 2
Memory area 3
PV
6 min.
6 min.
9 min. *
b
a
c
Time
* In this example, the Area soak time for Memory
area 3 is set. However, as the Area soak time for
the memory area linked last becomes invalid, the
state of SV3 reached continues.
The unit time can be changed by the Setting
change rate limiter and the Soak time unit
selection in the Engineering mode. (P.97)
Input 1_setting change rate limiter (down)
setting screen
AREA
Factory set value:
OFF (Unused)
AREA
Factory set value:
OFF (No link)
Link area number setting screen