8. ENGINEERING MODE
IMR01N12-E7
84
Event action at input error (EEo1, EEo2, EEo3, EEo4)
Event action at input error is to select the Event action when the measured value reaches the Input error
determination point (high or low limit).
Data range:
0:
Normal
processing
1: Turn the event output ON
Factory set value:
0
Related parameters:
Input error determination point (high) (P. 70),
Input error determination point (low) (P. 71)
Event action at input error:
Example: Input range:
0 to 250.0 MPa
Input error determination point (high): 240.0 MPa
Input error determination point (low): 5.0 MPa
Action area at input error
Action area at input error
Differential gap
(0.1 % of input span)
Input error determination point
(high)
0.0 MPa
5.0 MPa
240.0 MPa
Forcibly turned on
1
250.0 MPa
Select one of these
Select one of these
Normal processing
Manipulated output value
(MV)
obtained by control-computing
a measured value (PV)
Normal processing
2
1
The event output is forcibly turned on regardless of the event action status when the input is abnormal.
Forcibly turned on
1
Normal processing
2
2
The event output is produced depending on the selected event action status even if the input is abnormal.
Input error determination point
(low)
Input scale range
Event assignment (EVA1, EVA2, EVA3, EVA4)
Use to assign event outputs to either Input 1 or Input 2.
Data range:
1:
For
Input
1
2: For Input 2
Factory set value:
1
Related parameters:
Event type selection (P. 80), Event hold action (P. 82), Event differential gap (P. 83),
Event action at input error (P. 84), Event set value (P. 35)