APPENDIX
IMR01N12-E7
A-
17
Function block F41: Event 1
Name Parameter Data
range
Factory set
value
User set
value
Page
Event 1 type selection
(ES1)
0: None
1: Deviation
high
2: Deviation
low
3: Deviation
high/low
4: Band
5: Process
high
6: Process
low
7: SV
high
8: SV
low
0
P.
80
Event 1 hold action
(EHo1)
0: OFF
1: ON
2: Re-hold action ON
0
P.
82
Event 1 differential gap
(EH1)
0 to Input span
(Varies with the setting of the
Decimal point position)
Pressure sensor
input:
2.0 MPa
TC/RTD:
2.0
C [
F]
V/I: 0.2 % of
input
span
P.
83
Event 1 action at input error
(EEo1)
0: Normal
processing
1: Turn the event output ON
0
P.
84
Event 1 assignment
(EVA1)
1: For Input 1
2: For Input 2
1
P.
84
Function block F42: Event 2
Name Parameter Data
range
Factory set
value
User set
value
Page
Event 2 type selection
(ES2)
0: None
1: Deviation
high
2: Deviation
low
3: Deviation
high/low
4: Band
5: Process
high
6: Process
low
7: SV
high
8: SV
low
0
P.
80
Event 2 hold action
(EHo2)
0: OFF
1: ON
2: Re-hold action ON
0
P.
82
Event 2 differential gap
(EH2)
0 to Input span
(Varies with the setting of the
Decimal point position)
Pressure sensor
input: 2.0 MPa
TC/RTD:
2.0
C [
F]
V/I: 0.2 % of
input
span
P.
83
Continued on the next page.