6. PARAMETER SETTING MODE
IMR01N12-E7
41
Link area number (LnKA)
Link area number is used for Ramp/Soak control function in conjunction with Area soak time and Setting change
rate limiter (up/down).
Data range:
OFF (No link)
1 to 16
Factory set value:
OFF
Related parameters:
Setting change rate limiter (up) (P. 38), Setting change rate limiter (down) (P. 39),
Area soak time (P. 40), Memory area soak time monitor (P. 107)
Ramp/Soak Control Function:
Ramp/Soak control is possible by using Area soak time, Link area number and Setting change rate
limiter (up/down) in Parameter setting mode.
* The Area soak time for the memory area linked last becomes invalid to continue the state of the Set value (SV) reached.
[Usage example]
Area soak time of
memory area 1
Area soak time of
memory area 2
Setting change rate limiter
(down) of memory area 3
Area soak time of
memory area 3
*
Measured value (PV)
Set value (SV) of
memory area 2
Set value (SV) of
memory area 1
Set value (SV) of
memory area 3
Present set value (SV)
Time
Memory area 2
Memory area 3
Memory area 1
Setting change
rate limiter (up)
of memory area 2
Setting change
rate limiter (up)
of memory area 1