8. ENGINEERING MODE
IMR01N12-E7
75
Continued from the previous page.
RUN/STOP transfer
Mode select from front key
or communication
Status of event input (DI)
Actual operation mode
STOP display
RUN (Control RUN)
Contact closed
RUN (Control RUN)
STOP is not displayed
Contact open
STOP (Control STOP)
Contact closed
STOP (Control STOP)
Contact open
Auto/Manual transfer
Mode select from front key or
communication
Status of event input (DI)
Actual operation mode
Display lamp
Auto
Contact closed
Auto
MAN mode lamp ON
Contact open
Manual
Contact closed
Manual
MAN mode lamp OFF
Contact open
Remote/Local transfer
Mode select from front key or
communication
Status of event input (DI)
Actual operation mode
Display lamp
Remote
Contact closed
Remote
REM mode lamp ON
Contact open
Local
Contact closed
Local
REM mode lamp OFF
Contact open
Transfer timing of RUN/STOP, Auto/Manual, and Remote/Local:
The selection operation is taken when DI contact is closed from the open condition (Rising edge).
* To make contact activation valid, it is necessary to maintain the same contact
state (contact closed) for more than 200 ms.
Contact open
Contact closed *
Rising edge