8. ENGINEERING MODE
IMR01N12-E7
70
Input scale low (1. PGSL, 2. PGSL)
This value is to set the low limit of the input scale range.
Data range:
Pressure sensor input:
Minimum value of the selected input range to Input scale high
TC/RTD inputs:
Minimum value of the selected input range to Input scale high
Voltage (V)/Current (I) inputs:
19999 to
99999
(Varies with the setting of the decimal point position)
Factory set value:
Input 1_input scale low (1.PGSL):
Pressure sensor input:
0.0
Voltage (V)/Current (I) inputs: 0.0
Input 2_input scale low (2.PGSL):
TC/RTD inputs:
Minimum value of the selected input range
Voltage (V)/Current (I) inputs: 0.0
Related parameters:
Input type selection (P. 66), Decimal point position (P. 69), Input scale high (P. 67)
Input Scale Low function:
The input scale range can be easily set by setting the Input scale high/low.
When a Voltage/Current input type is selected, the Input scale high can be set lower than the Input
scale low. (Input scale high
Input scale low)
Input error determination point (high) (1. PoV, 2. PoV)
Use to set Input error determination point (high). Input error determination function is activated when a
measured value reaches the limit, and control output value selected by Action at input error will be output.
Data range:
Input scale low
(5 % of input span) to Input scale high
(5 % of input span)
Factory set value:
Input 1_input error determination point (high) (1. PoV):
Pressure sensor input:
Input scale high + (5 % of input span)
Voltage (V)/Current (I) inputs: 105.0
Input 2_input error determination point (high) (2. PoV):
TC/RTD inputs:
Input scale high
(5 % of input span)
Voltage (V)/Current (I) inputs: 105.0
Related parameters:
Input error determination point (low) (P. 71), Action at input error (high) (P. 89),
Action at input error (low) (P. 89), Manipulated output value at input error (P. 90)